12/20(24)kV XLPE Insulated PVC Sheathed Unarmoured Power Cable

Single Core (Unarmoured )

Conductor
Conductor
screen

( mm )
Insulation
thickness

( mm )
Insulation
screen

( mm )
Copper
screen
tape
( mm )
Sheath
thickness

( mm )
Overall
diameter
approx.
( mm )
Cable
weight
approx.
( kg/km )
Insulation
resistance at
15.6∑C (Min.)
( Mohm/km)
Size

(mm)
Shape

Outside
diameter
( mm )
35
50
70
95
120
C.C.
C.C.
C.C.
C.C.
C.C.
6.95
8.05
9.67
11.39
12.33
0.8
0.8
0.8
0.8
0.8
5.5
5.5
5.5
5.5
5.5
0.8
0.8
0.8
1.0
1.0
0.1
0.1
0.1
0.1
0.1
1.8
1.8
1.9
2.0
2.0
27.5
28.7
30.4
32.7
34.3
1007
1165
1426
1771
2064
2200
2000
1800
1600
1500
150
185
240
300
400
C.C.
C.C.
C.C.
C.C.
C.C.
14.24
15.98
18.32
20.65
23.33
0.8
0.8
0.8
0.8
0.8
5.5
5.5
5.5
5.5
5.5
1.0
1.0
1.0
1.0
1.0
0.1
0.1
0.1
0.1
0.1
2.0
2.1
2.2
2.3
2.4
35.8
37.7
40.2
42.7
45.6
2377
2799
3443
4117
5023
1400
1300
1200
1100
1000
500
630
C.C.
C.C.
26.34
30.50
0.8
0.8
5.5
5.5
1.0
1.0
0.1
0.1
2.5
2.6
49.0
53.5
6105
7653
900
800


3 Core (Unarmoured )

Conductor
Conductor
screen

( mm )
Insulation
thickness

( mm )
Insulation
screen

( mm )
Copper
screen
tape
( mm )
Sheath
thickness

( mm )
Overall
diameter
approx.
( mm )
Cable
weight
approx.
( kg/km )
Insulation
resistance at
15.6∑C (Min.)
( Mohm/km)
Size

(mm)
Shape

Outside
diameter
( mm )
35
50
70
95
120
C.C.
C.C.
C.C.
C.C.
C.C.
6.95
8.05
9.67
11.39
12.33
0.8
0.8
0.8
0.8
0.8
5.5
5.5
5.5
5.5
5.5
0.8
0.8
0.8
1.0
1.0
0.1
0.1
0.1
0.1
0.1
2.7
2.8
3.0
3.1
3.2
57.4
60.0
63.8
68.7
72.0
3404
3919
4768
5897
6844
2200
2000
1800
1600
1500
150
185
240
300
400
C.C.
C.C.
C.C.
C.C.
C.C.
14.24
15.98
18.32
20.65
23.33
0.8
0.8
0.8
0.8
0.8
5.5
5.5
5.5
5.5
5.5
1.0
1.0
1.0
1.0
1.0
0.1
0.1
0.1
0.1
0.1
3.3
3.4
3.6
3.8
4.0
75.3
79.3
84.8
90.2
96.4
7853
9211
11275
13441
16339
1400
1300
1200
1100
1000


3 Core (Steel Wire Armoured)

Conductor
Insulation
thickness

( mm )
Copper
screen
tape
( mm )
Inner
sheath
thickness
( mm )
Armour
wire
diameter
( mm )
Outer
sheath
thickness
( mm )
Overall
diameter
approx.
( mm )
Cable
weight
approx.
( kg/km )
Insulation
resistance at
15.6∑C (Min.)
( Mohm/km)
Size

(mm)
Shape

Outside
diameter
( mm )
50
70
95
120
150
C.C.
C.C.
C.C.
C.C.
C.C.
8.05
9.67
11.39
12.33
14.24
5.5
5.5
5.5
5.5
5.5
0.1
0.1
0.1
0.1
0.1
1.6
1.6
1.6
1.6
1.6
2.5
2.5
2.5
2.5
3.15
2.9
3.0
3.1
3.2
3.4
66
70
73
77
82
6960
7980
9170
10300
12500
2000
1800
1600
1500
1400
185
240
300
C.C.
C.C.
C.C.
15.98
18.32
20.65
5.5
5.5
5.5
0.1
0.1
0.1
1.8
1.8
1.8
3.15
3.15
3.15
3.5
3.6
3.8
86
91
97
14100
16500
19000
1300
1200
1100


3 Core
(Steel Tape Armoured)

Conductor
Insulation
thickness

( mm )
Copper
screen
tape
( mm )
Inner
sheath
thickness
( mm )
Armour
tape
diameter
( mm )
Outer
sheath
thickness
( mm )
Overall
diameter
approx.
( mm )
Cable
weight
approx.
( kg/km )
Insulation
resistance at
15.6∑C (Min.)
( Mohm/km)
Size

(mm)
Shape

Outside
diameter
( mm )
50
70
95
120
150
C.C.
C.C.
C.C.
C.C.
C.C.
8.05
9.67
11.39
12.33
14.24
5.5
5.5
5.5
5.5
5.5
0.1
0.1
0.1
0.1
0.1
1.6
1.6
1.6
1.6
1.6
0.5
0.5
0.5
0.5
0.5
2.8
2.9
3.0
3.2
3.3
63
67
70
74
78
5370
6240
7340
8350
9530
2000
1800
1600
1500
1400
185
240
300
C.C.
C.C.
C.C.
15.98
18.32
20.65
5.5
5.5
5.5
0.1
0.1
0.1
1.8
1.8
1.8
0.5
0.5
0.8
3.4
3.5
3.7
82
87
94
11000
13100
16500
1300
1200
1100

website: www.caledonian-cables.com